Vietnam Factory introduction: Low voltage distribution cabinet installation equipment and material requirements?
1, the iron distribution cabinet body is galvanized plate, and should have a certain mechanical strength, distribution box layer plate thickness is not less than 1.5 mm galvanized iron plate. The plastic distribution box has a certain mechanical strength, the perimeter is flat without damage, and the thickness of the two-layer board is not less than 8 mm. The wooden distribution box should be brushed with anti-corrosion and fireproof paint, and the thickness of the wooden panel is not less than 20 mm.
2. The protective conductor in the cabinet shall have a bare terminal connecting to the external protective conductor. If the design does not require it, the minimum cross-sectional area SP of the protective conductor in the cabinet shall not be less than that specified in Table 1.
A, the cabinet low-voltage electrical combination should meet the following requirements:
a, the heating element is installed in a good heat dissipation position;
B. The melt specifications of the fuse and the setting value of the automatic switch meet the design requirements;
c, the switch plate contact is good, there is a safe distance between the adjacent plates, the switch does not touch the adjacent plate;
d, signal circuit signal lights, buttons, optical plates, electric bells, electric whistles, accident clocks and other actions and signals display accurately;
e, the shell needs to be grounded (PE) and zero (PEN), reliable connection;
f. The terminal block is firmly installed, the terminal number is in order, the strong and weak terminals are isolated, and the terminal specifications are compatible with the cross-sectional area of the core wires.
B, cabinet wiring:
a, the current circuit adopts the rated voltage of not less than 750V, core section of not less than 2.5mm2 copper core insulated wire or cable;
B. Except for electronic component circuits or similar circuits, the wires of other circuits shall be copper core insulated wires or cables with a rated voltage of not less than 750V and a core section of not less than 1.5mm2;
c, the secondary circuit connections should be bundled, different voltage levels, AC, DC lines and computer control lines should be bundled and marked; The fixing shall not prevent the pulling out or pushing in of the hand switch or withdrawable component.
d, wiring is strictly prohibited to use open nose.
C, connecting cabinets, boxes on the electrical appliances and consoles, boards and other moving parts of the wire should meet the following requirements:
a, the use of multi-core flexible wire, laying length with appropriate margin;
b, the wire harness has a protective insulation layer such as a plastic tube coat;
c, when connected with electrical appliances, the end is twisted tightly, and there is a non-open terminal terminal or tin, not loose, broken;
d, the two ends of the rotating part are fixed with clips.
e, box, cabinet Angle iron, flat iron, screws, nuts, gaskets, etc. are galvanized products.
D. Materials used for installing the power distribution cabinet:
a, the steel should have no obvious rust, and there is material proof;
b, galvanized screws, galvanized bolts, nuts, spring pads, flat pads;
c, other materials: lead wire, phenolic board, phase paint, anti-rust paint, mixed paint, plastic cable tie, plastic hose, shaped plastic hose, nylon cassette, small white wire, insulating rubber pad, sign plate, enjoining electrode, saw blade, oxygen, acetylene, etc., should meet the quality requirements.
E. Install the main equipment of the PDC
a, lifting and handling equipment: car, car crane, trolley, hoist, chain, wire rope, hemp rope, etc
b. Installation tools: bench drill, electric drill, electric hammer, grinding wheel, bench vice, file, hacksaw, hammer, wire cutter, screwdriver, polishing machine, electric welding machine, gas welding tools, wrenches, electrical tools, etc.;
c, test tools: level, steel ruler, feeler, level line drop feeler, megohm meter multimeter steel ruler test pen steel tape measure, etc.
F. Operating conditions for installing a PDC
a, low voltage distribution cabinet installation:
1, civil engineering construction elevation, size, structure and embedded parts meet the design requirements.
2, wall, roof spraying is completed, no water leakage, doors and Windows installed, the door locked.
3, the indoor ground construction is completed, the site is clean and the road is smooth.