Industry News
What are the requirements for customizing frequency converter control cabinets in Thailand?

What are the requirements for customizing frequency converter control cabinets in Thailand?

Customizing frequency converter control cabinets in Thailand requires comprehensive consideration of technical standards, environmental adaptability, regulatory certifications, and other key aspects. Below is a detailed breakdown:

I. Technical Standards and Certifications

Voltage and Frequency

Compatible with 220V/380V AC±10% and 50Hz power grids, supporting three-phase five-wire systems (L1/L2/L3/N/PE).

Frequency converters must match motor power (e.g., 0.75–500kW) and be compatible with control signals like 4–20mA and Modbus.

Mandatory Certifications

TISI Certification: Compliance with standards such as TISI 60439 (low-voltage equipment) and TISI 60204 (mechanical safety).

EMC Compliance: Pass NBTC electromagnetic compatibility tests (CISPR 22/24).

RoHS Directive: Restriction of hazardous substances such as lead and mercury.

II. Environmental Adaptability Design

Climatic Protection

High Temperature and Humidity: Force air-cooling (fans with IP54 protection) or water-cooling systems to maintain cabinet temperature ≤40°C; equip with heating dehumidifiers (activated at humidity >75%).

Corrosion and Dust Resistance: Cabinets coated with epoxy resin (thickness ≥80μm), components made of stainless steel/nickel-plated materials; IP55 for outdoor use, IP44 for indoor use.

Heat Dissipation and Layout

Sufficient heat dissipation space for frequency converters; maintain a distance of ≥30cm between power and signal cables to avoid electromagnetic interference.

III. Electrical Safety and Wiring

Grounding Requirements

Protective grounding (PE) resistance ≤4Ω, with independent grounding for frequency converters; yellow-green grounding wires must have a cross-sectional area ≥50% of phase wires (copper).

Circuit Specifications

Cables must be PTT-certified flame-retardant (e.g., PVC/XLPE insulation) with Thai/English wire numbering; terminal blocks 预留 20% spare positions.

Equipped with circuit breakers, thermal relays, and phase-loss protection; emergency stop buttons must be red mushroom-type, directly cutting power.

IV. Operation Interface and Functions

Human-Machine Interaction

Operation panels support bilingual Thai/English displays, with ≥7-inch touchscreens showing real-time parameters like frequency and current.

Alarm logs stored for ≥30 days, audible-visual alarms ≥85dB, and support for Modbus/Profibus communication to integrate with DCS systems.

Safety Protection

Door interlock switches to cut high voltage when opened; Thai warning labels (e.g., "อันตราย! ติดไฟ").

V. Localization and Compliance

Documentation and Services

Provide Thai-language operation manuals, circuit diagrams, and TISI certification documents; suppliers must have after-sales centers in Thailand for 24-hour support.

Cost and Delivery

Consider import tariffs (5%–10%) and VAT (7%), with local assembly recommended; customization lead time 6–12 weeks, avoiding rainy-season logistics (May–October).

Key Recommendations

Prioritize brands like Siemens or Danfoss with TISI certification, and collaborate with local Thai engineering companies for installation and commissioning to ensure compliance with PEA (Power Engineering Authority of Thailand) and factory safety standards.


Return